Mactor – 11KV
Mactor is a solid dielectric single pole vacuum circuit breaker with in built current and voltage sensors and vacuum interrupters operated with time proven magnetic actuator mechanism. This outdoor Vacuum circuit breaker is aimed to improve the reliability and quality of power with the maintenance benefits of a solid dielectric insulated device. equipped with automatic and manual trip operation, Mactor are ideally suited for primary, secondary and distribution substations.
Embedded Current and Voltage Sensors
Current sensors and voltage sensors are a direct replacement to current and potential transformers. When incorporated into Metal clad switchgear it makes your switchgear failure free.
Embedded Current and Voltage Sensors
Current and voltage sensors are designed for both metering and protection, covering all your specification in one design with added benefits.
Protection Class: 5P40
Metering: 0.2s
Hydrophobic cycloaliphatic epoxy bushing (HCEP)
FEATURES AND BENEFITS
Circuit Breaker Configurations
- Three phase mechanically ganged
- Three phase independent operated
Mounting Configurations
- Pedestal mount
- Pole mount
System Voltage | 12kV | 24kV/36kV |
---|---|---|
Rated Voltage | 12kV | 24kV/36kV |
Rated normal Current | 1250A/1600A | 1250A/1600A |
Short time current withstand capacity | 25kA | 25kA |
Rated Frequency | 50Hz. | 50Hz. |
Power frequency withstand voltage | 28kV(rms) | 70kV(rms) |
Lightning impulse withstand voltage | 75kV peak | 170kV peak |
Short circuit breaking current for circuit breaker | 25kA/3Sec | 25kA/3Sec |
Short circuit making current for circuit breaker | 62.5KA | 62.5KA |
Degree of protection (outdoor) | IP65 | IP65 |
Design ambient temperature | 50 ̊C | 50 ̊C |
Rated insulation level | 12/28/75 | 36/70/170 |
Operating Sequence | O-.3S-CO-3M-CO-3M-CO | O-.3S-CO-3M-CO-3M-CO |
Dielectric medium | Solid Dielectric Medium | Solid Dielectric Medium |
Breaking medium | Vacuum | Vacuum |
Operating Mechanism | Magnetic Actuator | Magnetic Actuator |
Mechanical life | 1,00,000 Operations | 1,00,000 Operations |
Electrical life at rated current | 100 Operations | 100 Operations |
Auxiliary voltage | 24V | 24V |
Relevant standards | IEC 62271-100, IEC 62271-200 | IEC 62271-100, IEC 62271-200 |
Installation | Single pole, Two pole and Pedestal | Single pole, Two pole and Pedestal |